SEGURTO (MV) SWITCHGEAR
SEGURTO BZ48 14kV Switchgear
According to the cabinet structure, SEGURTO BZ48 14kV Switchgear can be divided into four categories: metal enclosed armored switchgear, metal enclosed interval switchgear, metal enclosed box switchgear, and open switchgear. The main components of metal enclosed armored switchgear, such as circuit breakers, transformers, busbars, etc., are respectively installed in grounded metal partitions separated by metal enclosed switchgear. Metal enclosed switchgear in that its main electrical components are also installed in separate compartments, but have one or more non-metallic partitions that meet a certain level of protection.
Technical Data
Standards
- Standards Designed and Tested in Third-Party Labs to IEC and IEEE Standards UL
- Witnessed and STL Certified to IEC 62271-100 and -200
- Voltage - 14 kV
- Lightning Impulse Withstand Voltage - 95 kV
- Power Frequency Withstand Voltage - 38 kV
- Rated Frequency - 50/60 Hz
- Internal ARC Class - AFLR
- Loss of Service Continuity Category - LSC2B
- Circuit Breaker Compartment - Interlocked-Controlled
- Busbar Compartment - Tool-Based/Non-Accessible
- Cable Compartment - Tool-Based or Interlock-Controlled
- External Degree of Protection - IP4X (IP41 as an Option)
- Primary Live Parts (Tank) Degree of Protection - IP65
- Installation - Indoor
- Rated Normal Current - 2000* A
- Rated Short-Time Withstand Current - 82 kA 1sec (3sec) 2)
- Rated Peak Withstands Current - 65 kA
- Rated Normal Current - 2500* A
- Rated Short-Circuit Breaking Current - 31.5 kA
- Rated Short-Circuit Making Current - 82 kA
- Rated Short-Time Withstand Current - 31.1 kA 1sec (3sec) 2)
- Breaking Number of Short-Circuit Current - 400
- Rated Operating Sequence - 0 - 0.9s - CO - 19s - CO
System
Accessibility of Compartments
Busbar System
Circuit Breaker Ratings
Mechanism
*Consult Control Equipment Representative for Higher Ratings