SUIVON (MV) SWITCHGEAR
Suivon T20 24kV Switchgear
All Suivon medium voltage switchgears are specifically designed and manufactured to meet the environmental and safety conditions of the marine and offshore industries. Suivon’s reputation throughout the marine and offshore industry ensures that reliability and safety are of prime importance in the design and manufacture of the HS21 medium voltage switchboard.
Technical Data
Standards
- Standards Designed and Tested in Third-Party Labs to IEC and IEEE Standards UL
- Witnessed and STL Certified to IEC 62271-100 and -200
- Voltage - 24 kV
- Lightning Impulse Withstand Voltage - 125 kV
- Power Frequency Withstand Voltage - 50 kV
- Rated Frequency - 50/60 Hz
- Internal ARC Class - AFLR
- Loss of Service Continuity Category - LSC2B
- Circuit Breaker Compartment - Interlocked-Controlled
- Busbar Compartment - Tool-Based/Non-Accessible
- Cable Compartment - Tool-Based or Interlock-Controlled
- External Degree of Protection - IP4X (IP41 as an Option)
- Primary Live Parts (Tank) Degree of Protection - IP65
- Installation - Indoor
- Rated Normal Current - 2000* A
- Rated Short-Time Withstand Current - 6.1 kA 1sec (3sec) 2)
- Rated Peak Withstands Current - 15.6 kA
- Rated Normal Current - 2000* A
- Rated Short-Circuit Breaking Current - 50** kA
- Rated Short-Circuit Making Current - 15.6 kA
- Rated Short-Time Withstand Current - 6.1 kA 1sec (3sec) 2)
- Breaking Number of Short-Circuit Current - 200
- Rated Operating Sequence - 1 - 2.3s - CO - 30s - CO
System
Accessibility of Compartments
Busbar System
Circuit Breaker Ratings
Mechanism
*Consult Control Equipment Representative for Higher Ratings